科技締造品質(zhì),創(chuàng)新引領(lǐng)未來(lái)
Technology creates quality, innovation leads the future
(1)機(jī)械強(qiáng)度條件(2)發(fā)熱條件(3)電暈條件Sj=I ** x/JSj—經(jīng)濟(jì)截面;
I ** x—導(dǎo)線正常工作時(shí)的**作業(yè)電流
<span font-size:16px;background-color:#ffffff;"="" style="font-family: "sans serif", tahoma, verdana, helvetica; font-size: 12px; white-space: normal; color: rgb(48, 49, 51);">表5:軟導(dǎo)線經(jīng)濟(jì)電流密度經(jīng)濟(jì)電流密度核算出導(dǎo)線截面后,應(yīng)選定與核算經(jīng)濟(jì)截面最接近的標(biāo)稱截面,然后再依照3個(gè)必要條件進(jìn)行校驗(yàn)。對(duì)于電壓等級(jí)小于或等于35kV的配電線路,為滿足用戶對(duì)電壓等級(jí)的要求,還應(yīng)校驗(yàn)電壓損耗。舉例:某35kV架空線路,選用雙回鋼芯鋁絞線架起,線路長(zhǎng)15km,結(jié)尾**負(fù)荷為16MW,平均功率因數(shù)為0.9,正常狀況下容許**電壓損耗為5%。試選擇導(dǎo)線截面。解:按經(jīng)濟(jì)電流密度選擇導(dǎo)線截面,按3個(gè)必要條件及容許電壓損耗校驗(yàn)導(dǎo)線截面。**作業(yè)電流:I ** x=(P/2)/(1.732UNcosθ)=(16000/2)/(1.732×35×0.9)=146.63A由**作業(yè)電流:T ** x=2000h,查表5得經(jīng)濟(jì)電流密度J=1.65A/mm2。核算經(jīng)濟(jì)截面:Sj=I ** x/J=146.63/1.65=88.87mm2選擇最接近的截面:LGJ-95型導(dǎo)線,其參數(shù)是ro+jxo=0.332+j0.4Ω/km,長(zhǎng)期持續(xù)安全電流為335A。校驗(yàn):①機(jī)械強(qiáng)度:S=95mm2>Sy=25mm2,滿足要求。②發(fā)熱溫度:因雙回線路在工作中容許單回工作,此刻,線路流通電流增大,發(fā)熱加劇,為最惡劣工作狀況。在發(fā)熱溫度校驗(yàn)中應(yīng)考慮該工作方法。T ** x=2×146.63A=293.26<Iy=335A滿足要求。③電暈條件:由于線路為35kV,故不必驗(yàn)算電暈條件。④電壓損耗:△U=(PR+Q×)L/U=1.80kVU%=1.80/35=5.15%>5%不滿足要求應(yīng)增大導(dǎo)線截面。改組LGJ-120型導(dǎo)線,其參數(shù)是ro+jxo=0.236+j0.421Ω/km,長(zhǎng)期持續(xù)安全電流為380A。校驗(yàn):①機(jī)械強(qiáng)度:S=95mm2>Sy=25mm2滿足要求;②發(fā)熱溫度:I ** x=2×146.63A=293.26A<Iy,=380A查表知LGJ-95導(dǎo)線在缺點(diǎn)工作方法下**安全電流為335A大于導(dǎo)線中**電流,滿足要求。③電暈條件;由于線路為35kV,故不必驗(yàn)算電暈條件。④電壓損耗:△U=(PR+Qx)L/U=1.60kVU%=4.57%<5%滿足要求。